
![]()
![]()
![]()
A strong earthquake of
magnitude 7.7 (USGS revised) struck the Kutch area in
A week after the event, an EERI reconnaissance team was in the field for post-earthquake investigation work. The building group co-coordinated by Dr. Rakesh K. Goel of Calpoly, San Luis Obispo, CA, USA, and Dr. C. V. R. Murty of Indian Institute of Technology at Kanpur, India focused on building performance in Ahmedabad and other regions of Gujarat affected by the January 26 event. The other members of the EERI team were Alok Goyal, and Jaswant Arlekar. In addition, Rainer Metzger of PSM Consulting, and a team of three engineers from Degenkolb Engineers, led by Jeff Soulages, contributed to the efforts of the EERI team. Several other teams, which are in the field or will be visiting at a latter date, would also be invited to supplement the efforts of the EERI team. This abstract summarizes the findings on damage to engineered buildings in Ahmedabad. A detailed report and damage to non-engineered structures will be presented in a comprehensive report latter.
During the January 26, 2001
earthquake, numerous mid- to high-rise residential buildings collapsed in the
city of
It is useful to note the
significant length of the ground shaking; noticeable accelerations were
recorded for a duration of nearly two minutes. The shaking in the city of
Ahmedabad consisted of low levels of motion for about first 30 seconds followed
by a strong shaking phase lasting about another 30 seconds, and then a gentle
shaking again at the end (Figure 2). Discussions with residents of many
apartment complexes indicated that many people were able to run out during the
initial 30 seconds. The building collapses occurred a little after the onset of
the strong shaking phase. Therefore, the initial gentle shaking appeared to
have served as a warning signal and may be credited with saving many lives.

Figure 1. Map of

Figure 2. Accelerations recorded at the basement of the
passport building in Ahmedabad during the January 26 Bhuj
earthquake (Source:
The typical residential
construction in Ahmedabad consists of reinforced concrete moment resisting
frame system with un-reinforced brick infill panels. The frame at the ground
floor is open with floors at the upper floors containing un-reinforced brick
infill panels. This type of lateral load resisting system leads to what is
commonly known as a “soft-story” system (Figure 3). Most buildings also have
overhanging covered balconies at higher floors (Figure 4); the overhangs were
observed to be about 5 feet. The columns at the ground floor may not align with
the columns at the upper floors giving rise to vertical discontinuities in the
lateral load resisting system.

Figure 3. Example
of a soft-story apartment building (Photograph by Goel).
The above-described lateral load resisting system occurs because of two factors. First, the open ground floor is needed to provide car parking; the buildings are usually built on very small land lots with little room for open parking. Second, the Floor Surface Index (FSI) used by the local municipal corporation for residential construction permits the land developers to cover more area at upper floor than the ground floor. The FSI only counts the area of within the column footprints at the ground floor. As a result, the lateral load resisting system consists of only two to three columns in a frame on the ground floor with a beam overhanging on both sides. The upper floors may or may not continue these columns. But at least two floating columns are added, one on each end of the cantilever beam, starting from the first floor and running the entire height of the building.
The columns for low-rise residential buildings, up to ground plus four stories (G+4), rest on shallow isolated footings located about 5 feet below the ground level. For taller buildings, say up to ground plus ten stories (G+10), the column foundations are still open footings located at a depth of 8 to 10 feet; sometimes the foundation may also have tie beams. The column sizes for low-rise buildings (G+4) are about 9 inch by 18 inch with ties consisting of mild steel smooth No. 2 bars at a spacing of about 8 to 9 inches. The beams tend to be much deeper to accommodate large spans and overhangs giving rise to strong-beam, weak-column construction. The columns sizes for taller buildings (G+10) tend to be a little bigger, usually 12 inch by 24 inch with No. 3 deformed steel ties at a spacing of 8 to 9 inches. The beam size in taller buildings may be similar to the column size. The ties are always end up with a 90-degree hook.
The most residential buildings appear to be designed primarily for gravity load; there are some indications that the lateral loads may not have been properly considered in design of these buildings. There is insufficient confining steel to provide required ductility in the lateral load resisting system, and column reinforcement is spliced just above the beam level, with often in sufficient development length.
Most residential buildings in Ahmedabad suffered some type of damage during the earthquake. Much of the damage was in the form of cracking of infill wall panels at the ground floor level. However, nearly one hundred[1] residential buildings collapsed during January 26, 2001 event. Since for the ground motion experienced in the city, buildings with sound design and construction should not have experienced any structural damage (although some nonstructural damage may be expected), the damage appears to be due to a combination of factors. Based on the post-earthquake field investigation, following appear to be the technical reasons for the observed damage.
Soft-Story System. As
described previously, a large number of residential buildings in the city have
open ground floors leading to soft first story. Besides the elevator core,
there are few walls, if any to provide lateral resistance. The upper floor
frames are usually filled with un-reinforced brick masonry forming a very stiff
lateral load resisting system. Most of the collapses and significant damage
occurred in this type of soft-story buildings. It is well known from
observations after past earthquakes in

Figure 5. Half of the building with soft-story collapsed during the January 26, 2001 Bhuj earthquake (Photograph by Goel).
Insufficient Confinement. As described previously, the columns typically had very light confinement, in the form of No. 2 or No. 3 ties with a spacing of 8 to 9 inches and 90-deree hooks. With large deformation and resulting extreme shear demands that occur in ground floor columns of lateral load resisting system with soft first story, the provided confinement was insufficient. As a result ground floor columns failed in brittle shear mode, which led to catastrophic failure in most collapsed buildings. Many buildings that did not collapse showed signs of significant shear cracking in the columns, as evident in crossing (diagonal) cracks in columns of building shown in Figure 4.
Insufficient Shear Core
Details. In soft-story structures, the shear wall around the elevator is
usually relied upon to carry much of the lateral load at the ground floor
level. However, insufficient amount of shear wall core coupled with poor
quality of construction, improper reinforcement detailing, and insufficient
connection to the rest of the building contributed to poor performance of many
buildings. As evident from Figure 6, the shear core is usually connected to the
rest of the building by floor slabs only with no or very few beams. The
anchorage of the reinforcing steel from slab to the elevator core is
insufficient. As a result, the slabs just pull out clean from the core during
the collapse with the elevator core standing. In some situations, the may have
proved to be blessing in disguise as it may have saved the rest of the building
from collapsing. The shear core itself is about 4 to 6 inches thick with very
light reinforcement consisting of two layers of mesh formed with of No.3 or 4
bar at vertical and horizontal spacing of about 18 inches. This detailing may
have been insufficient to transfer the lateral load at the ground floor, as
evident from the severe cracking present in the shear core of the building
shown in Figure 7. The shear cracks in the elevator core of most building were
observed only at the ground floor, an indication that the first soft-story
system imposed large demands on the shear core at this floor.

Figure 6. Half of the building
pulled away from the elevator core that formed the shear core in the building
(Photograph by Goel).

Figure 7. Severe shear cracking in the ground floor shear core (Photograph by Goel).
Poor Quality of Material. Although
the factors listed above contributed to failure of many buildings, they alone
cannot be the sole cause. In may instances, only one
out of several similarly constructed buildings in the same apartment complex
collapsed; others while suffering significant damage did not collapse. This
indicates that poor quality of material may have been one of the main factors
that caused collapse of many buildings; the earthquakes are known to be
unforgiving in finding structural defects. Figure 8 shows bottom of a columns
in a partially collapsed building. The concrete has simply disintegrated within
the reinforcement cage; when touched, the concrete felt sandy with little
cement. Also note that the 90-degree hooks have opened up which leads to little
or no confinement of the concrete. Many of the times, the concrete cover to
reinforcement was noted to be less than half-inch; most of the cover was
provided by plaster used to smooth the columns surface. It is worth noting that
most of the water supply in the outer part of the city is through ground water
which is salty in taste. Usually the same water is used in preparing the
concrete for construction. Therefore, the presence of salts may have also
affected the concrete quality.

Figure
8. Poor quality of concrete (Photograph by Goel).

Figure 9. Part of the building shown in Figure 6 fell on the neighboring building indicating presence of torsional motions (Photograph by Goel).
Plan Asymmetry. In many situations, the buildings had significant asymmetry in the plan. The asymmetry usually resulted from uneven distribution of mass, which occurred after the building had been constructed. For example, there is some anecdotal evidence that in one of the buildings that collapsed during the earthquake event, owner of the building had built a swimming pool on one corner of the building. Since the type of residential building construction found in the city tends to be torsionally very flexible at the ground floor (usually shear wall core and a few columns provide the torsional rigidity), even slight eccentricities between the centers of mass and rigidity may lead to significant torsional motions. As a result, columns on one side of the building may experience excessive deformations. If not designed to accommodate these excessive deformations, they may fail leading to the buildings collapse. The excessive deformations due to torsion may have contributed to failure of at least one building. There is some physical evident to support this conclusion as half of the building shown in Figure 6 fell on the neighboring building shown in Figure 9, indicating that the portion that collapsed was moving more than the portion that was left standing. The direction of the building motion appears to be consistent with that expected due to eccentricity created by the swimming pool on one corner of the building.
Soil Conditions. The
localized soil conditions also contributed to the collapse of many buildings. A
thick alluvial deposit along the


Figure 10. Building damage
pattern and satellite image of the city of

|
File Name |
Location |
Description |
|
Sabarmati Ashram, Ahmedabad |
An overview of the Vinoba/Mira Kutir. This one-story, URM building was built in early 1900 and provided housing for two of the important followers of Mahatma Gandhi during his struggle for independence of India. The tiled roof is supported on timber purlins. This building suffered moderate amount of damage shown in next few photos. Although this site is located right next to the Sabarmati river, no other buildings on this complex suffered any noticeable damage. |
|
|
|
Cracks in the masonry just above the door frame. |
|
|
|
A vertical crack running from top of the door frame to the roof level. |
|
|
|
A big block of masonry fell out during the earthquake. The block has simply been grouted in its original place with cement mortar. |
|
|
|
A vertical crack developed at the corner due to separation of the two walls. |
|
|
|
Exposed rebars on underside of a beam show very little cover. Also notice the rusting in the rebars. |
|
|
|
Horizontal and vertical cracks in the
masonry wall due to separation from the frame and possible out-of-plane
bending. This type of cracks were widely observed in many buildings in the
city of |
|
|
|
Three monkeys used as an example by Mahatma Gandhi to illustrate his philosophy of speak no evil, see no evil, and hear no evil. |
|
|
Vidhya Laxmi Apartment, Near
Sabarmati Ashram and |
This ground plus four story (G+4) apartment complex is located very close to the Sabarmati river. Out of the two apartment blocks, one-half collapsed. This example building illustrates the typical construction details used for residential buildings. Typical construction is reinforced-concrete moment frame. The ground story is open to provide automobile parking, whereas frames at upper stories are filled with unreinforced masonry, usually 9 inch thick. This gives rise to a soft first story condition in the lateral load resisting system. |
|
|
|
Collapse of one-half of the apartment block. There were 5 casualties in during this collapse. |
|
|
|
This photograph shows a close-up view of the soft first story. Typical columns sizes are about 9 inch by 18 inch. Note sometimes arbitrary direction of the columns and a lack of uniform framing system, indicating design for gravity loads but not for earthquake (lateral) loads; the columns in the foreground appears to be an afterthought. Also note significant overhangs in upper floors. |
|
|
|
The columns typically had |
|
|
|
There appears to be insufficient lap length in column reinforcement. All rebars in columns are typically spliced just above the floor level. During failure, the upper columns simply pull out due to insufficient rebar lap lengths leading to pancake type collapses. |
|
|
|
There is a rush to retrofit buildings that did not collapse. The retrofit scheme in this apartment complex consists of adding 15 inch thick unreinforced masonry walls to minimize the soft first story condition, and jacketing some of the columns to increase their size by about 6 inches in both directions. The cost of retrofit is estimated to be about one-eight the building cost. |
|
|
|
A close-up view of the wall being added. Note that columns which are enclosed by the wall will not be jacketed. |
|
|
|
A column being prepared for jacketing. Note that outer plaster has not been removed; just the surface has been indented to provide bonding with the new concrete. |
|
|
Shivalaya Apartment Complex, |
This ground plus four story (G+4) apartment complex has two units. Both units suffered total collapse of the soft first story, that was used for parking. On elderly lady, who could not run out, died in this building during the earthquake. At the time of our visit, both units were being demolished. Note people on top of this building carrying out the demolition work eventhough the building is on the verge of collapse during an aftershock. |
|
|
|
A close-up view of the total collapse of the soft first story. |
|
|
|
The building had severe cracking in walls through out the height. This one is a total loss. |
|
|
Mansi Apartment Complex, Satellite Area |
One of the most publicized building failure, this ground plus ten story (G+10) residential-commercial complex experienced one of the most dramatic failure during the earthquake; 33 people are believed to have lost their lives in this building collapse. This photo shows one-half of one of the two units that collapsed. |
|
|
|
A close-up view of the collapsed portion of the building. Note the clean separation of the failed portion from the portion that remains standing. The two sides of the building were connected by the elevator core and the staircase well, except at the roof level where a penthouse spans both sides of the building. There were no cross beams connecting the elevator core and the staircase well to rest of the building. The anchor length of the reinforcement from the floor slab to the elevator core appears to be insufficient as the rebars just pulled out leaving a clean imprint on the elevator core. |
|
|
|
A close-up view of the elevator core and the stair well. |
|
|
|
The adjacent building was damaged when the collapsed portion of the Mansi Apartment fell on it indicating presence of torsional motions in the collapsed portion. The torsional motion appear to have resulted from uneven distribution of mass due to alleged construction of a swimming pool on one corner of the building at the penthouse level. |
|
|
|
A close-up view of the soft first story condition in the Mansi Apartment complex. The columns have very light transverse reinforcement in the form of #3 rebars at a spacing of about 9 inches. Note the overhang in upper stories, a typical detail used in residential construction to maximize covered area; the construction permit is granted based on the column footprints and the extra covered area above the ground floor due to overhanging portion is not counted. Also note shear cracking in the columns and arbitrary direction of the columns. |
|
|
|
Severe shear cracking in the shear wall that forms the elevator core at the ground floor level. There is no cracking above the ground floor, clearly indicating the high demands imposed at the ground floor level elements due to the soft first story condition. The reinforcement in the shear wall consisted of two layers of mesh with #4 rebars at vertical and horizontal spacing of about 18 inches. |
|
|
|
A close-up view of shear cracking in the elevator core shear wall. |
|
|
|
The damage to the shear wall is only in the first story; there is not sign of damage in upper stories. |
|
|
|
A temporary retrofit to provide gravity load support for columns in the building that did not collapse. |
|
|
|
Reinforcement cage for a column revealing very light transverse reinforcement. |
|
|
|
People retrieving their belongings from the portion of the building that remains standing. |
|
|
|
People are trying to retrieve whatever they can. In this case, a bookshelf being removed from the building. |
|
|
|
Articles retrieved are piled up next to the building. |
|
|
|
Priced possession of some young person is totally destroyed during the building failure. |
|
|
|
A crushed car that was pulled out from the building. |
|
|
|
A temple next to the collapsed building. The temple building appeared to have suffered no damage. Note the dust cloud from the debris being removed from the collapsed building just across the street. |
|
|
Shikhar Flats, Satellite Area |
A portion of this ground plus ten story (G+10) apartment complex collapsed during the earthquake. Once again, the lateral load resisting system had a soft first story condition. The building plan appear to be quite irregular, raising the possibilities of torsion contributing to the failure. Conversation with residents revealed that this building was constructed in parts over a period of several years. The collapsed portion was built on an adjoining playground. Nearly 100 people died in this failure. |
|
|
|
The clock stopped at approximately 8:46AM, the time of the earthquake. |
|
|
|
Remains of a child's bedroom. Note the dolls in a corner of the room. |
|
|
|
Photo shows significant overhangs. The circular balcony overhangs by about 8 feet from the nearest column line. Also visible is the retrofit of columns in progress. |
|
|
|
Details of column jacketing scheme being implemented. Note that the rebar cage has been built around the original columns. The ties were welded to the longitudinal rebars. The concrete on the columns has not been chipped to provide bond between the old and new concrete. Also note that the rebar cage ends at the beam soffit and does not extend into the foundation; it appears that there were no plans to strengthen the foundation in this case. |
|
|
Apollo Apartments, Kochrab Area |
Apollo Apartment complex consists of four 3 story + ground units. The construction is reinforced concrete moment frame with strong-beams and weak-columns, and open ground floor, typical of soft first story construction practice in the city. Out of the four units, which are about 20 years old, two collapsed. This photos shows the complete failure at the ground floor and pancaking of the second floor on the first floor. |
|
|
|
A close-up view of the pancaked story. People are trying to see if they can retrieve anything from the pancaked story. |
|
|
|
Debris being removed from the collapse site. |
|
|
|
This is a nine-story reinforced concrete building. The first two floors have showrooms/shops and the upper seven floors have office space. The plan of upper seven stories is T-shaped. The actual column lines are about 4.5 ft inside the façade; the façade is unreinforced brick infill supported on overhangs. The building suffered extensive cracking of the brick infills; the damage to the framing elements appeared to be minimal. Due to irregular shape (T-shape) of the building, torsional motions appear to have contributed to the damage. Note that most of the damage is to walls on the outer face of the side that is farthest away from the center of rigidity, i.e., the flexible side of the building. |
|
|
|
A close-up view of the damage to the brick infill. Note diagonal shear cracks in the wall, indicating that the wall, although considered non-structural and ignored in most analysis, participated in providing resistance and energy dissipation during the earthquake. |
|
|
Siddhashila Apartment, Vejalpur Area |
Damage pattern in typical ground plus four (G+4) story residential construction. This photo shows damage near the top of the column at the ground floor in a strong beam, weak column, soft-first story type construction. Note slight buckling of one of the longitudinal bars and rupture of the other bar. |
|
|
|
Note the beam in the transverse direction which is significantly stronger (deeper) compared to the columns. |
|
|
|
This figure shows the overhang above the ground floor typical of residential construction in Ahmedanad. Also note the deep beam compared to the columns to your left and the relatively shallow beam on the right. The column at the junction of the two beams experienced some damage. |
|
|
|
The column may be covered with about half-inch of mortar plaster. This photo shows the construction joint just below the beam soffit, which becomes visible when the plaster is removed. |
|
|
|
The shear wall core around the staircase took a significant beating in many low-rise residential buildings. In this case, diagonal cracks typical of those due to shear are clearly visible. |
|
|
|
Shear cracks in cantilever beam that supports the floating column at its tip starting from first floor up; cracks have been highlighted by a marker. These cracks develop due to a large vertical (axial) force from the floating column that needs to be transferred to the columns at the ground floor. Note that to prevent further damage, a temporary support columns has been added at the tip of the cantilever. While this column would aid in transfer of vertical load from the floating column above, it may lead to creation of the short, shear-critical beam, which may fail in brittle manner in the absence of sufficient shear reinforcement. |
|
|
|
Shear cracks were noted on both side of the beam. |
|
|
|
Concrete has completely disintegrated within the reinforcing cage. The quality of concrete appeared to be very poor upon visual examination; there was very little cement content in the concrete. The lateral reinforcement consisted of #2 ties at approximately 9 inch spacing. |
|
|
|
Overall buckling of the longitudinal bars. It appears that once the concrete crushed, there was very little vertical load carrying capacity in the columns and the entire reinforcing cage buckled. |
|
|
|
The 90 degree hooks in the lateral reinforcement do not work very well in columns of lateral load resisting systems. They simply open up and permit buckling of the longitudinal reinforcement. Note that due to opening of the middle tie, the longitudinal bar to your right has buckled between the ties above and below. Also note the buckling of the second longitudinal bar from your left between the two consecutive ties, indicating excessive tie spacing. |
|
|
|
Close-up view of the column with ties with open 90 degree hook. |
|
|
|
Close-up view of another column where the concrete has completely disintegrated between the reinforcement cage. |
|
|
|
An example of complete pancake type collapse of reinforced concrete moment frame building. This building fell on the neighboring building shown in the background causing minor damage that building. |
|
|
|
Well designed and well constructed structures like this television tower performed well and escaped with no damage during the earthquake. A neighboring studio building suffered significant cracking of the unreinforced brick masonry walls. |
|
|
Adalaj, 15 Km North of Ahmedabad |
This five-hundred year old stone block structure, known as Step Wells of Adalaj, suffered no damage during the earthquake. This structure is four-story tall at some locations. |
|
|
|
Life is coming back to normal after about a week in the area as evident from the visitors to the Adalaj Step Wells. |
|
|
|
The brick masonry in this five-hundred year old structure has stood the test of time. Except for spalling of cover mortar, which did not occur during the earthquake, there is no evident of deterioration of the masonry arches shown here. |
|
|
|
A close-up view of the brick masonry. Note the thick mortar joints between the walls. |
|
|
|
The 11th century |
|
|
|
This photo shows the below ground water
reservoir, which is empty now, next to the |
|
|
|
The walls of the |
|
|
|
The pre-existing vertical crack appears to have opened up a little more during the earthquake. |
|
|
|
Signs of slight movement at a corner of the structure. |
|
|
|
This close-up shows ornate carvings on the
walls of the |
|
|
|
Underside of the dome in the main temple building. |
|
|
|
Pre-existing cracks in the ring beam of the dome being monitored with glass strips pasted across the crack. One of the two strips cracked, indicating some movement during the earthquake. |
|
|
|
Life goes on. |
![]()
Back to the Home Page of Rakesh K. Goel
[1] The number of buildings collapsed or near collapse is approximate. The exact number will become available after the local authorities have completed a block-by-block survey of the entire building stock in the city.